Home Products Protection Relays DRAGON 1RMI 401D1 Multifunction motor protection

RMI 401D1 Multifunction motor protection

RMI 401D1 is a powerful Protection & Control IED for medium (from 0.5 to 2 MW) and small sized (from 0.1 to 0.5 MW) Motors with directional earth fault, voltage & frequency and motor protection functions. The device is designed as a main protection IED for asynchronous and synchronous motors. Depending on the requirements RMI 401D1 can be used also as a basic generator protection unit.

The protection is suitable for all types of current transformers - iron-core and linearized (Rogowski coil).

RMI 401D1 consists of IED type of DRAGON 1 and additional I/O module RTB-2.

All relay protection functions meet ANSI and IEC standards’ requirements:

  • Starting time supervision
  • Number of starts limitation
  • Stalled Rotor Protection function
  • Loss of load protection
  • Cooling failure protection
  • Three stages directional/non-directional definite time/instantaneous overcurrent protection
  • Directional/non-directional Inverse time overcurrent protection with 12 inverse time characteristics
  • Three stages directional/non-directional definite time/instantaneous ground fault protection
  • Directional/non-directional Inverse time ground fault protection with 12 inverse time characteristics
  • Definite time undercurrent protection
  • Negative Sequence overcurrent protection
  • Phase discontinuity protection
  • Three stages definite time over voltage protection
  • Three stages definite time under voltage protection
  • Two stages negative sequence over voltage protection
  • Directional overpower protection
  • Directional underpower protection
  • Three stages neutral voltage displacement
  • Four stages definite time over frequency protection
  • Four stages definite time under frequency protection
  • Four stages definite time rate of change of frequency protection
  • Thermal overload protection
  • Voltage vector shift protection
  • Arc protection
  • Voltage circuits supervision
  • Breaker failure protection
  • Clockwise and anticlockwise phase rotation function
  • Trip circuits supervision
  • Current circuits supervision functions
  • Circuit breaker life time monitoring

Automation and remote control functions

Disturbance (Fault) Recorder

  • Sampling rate – 1 kHz/4kHz
  • User defined trigger conditions and records duration
  • Recording mode -overwrite (ring buffer) or saturate
  • Each sample consists of instantaneous values of all analog and digital values

Event Recorder

  • Up to 1000 records
  • Each event consists of information about the event’s type, some additional data (such as pick-up current, voltage, the time elapsed and so on) and the time stamp of the event (year, month, day, hour, minute, second, millisecond)
  • Recording mode - overwrite

Protocols

  • Configuration tool - ROCON MMI protocol
  • SCADA communication - IEC 60870-5-103, MODBUS

Configuration, setting and administration

 

--------
Note: All flyers are subject to regular update