Multifunctional relay protection, automatics and remote control
RFI 401


Description
Technical data
Connection diagram
Optional possibilities



 


Description

General information

RFI 401
is intended to be used like a multifunctional relay protection, automatics and remote control units for middle voltage feeders and also like back-up protections for low voltage sides of the power transformers. For line protection, the device can be used in networks with grounded, low resistance grounded, isolated or compensated neutral point. It is suitable for radial systems with single-end infeed or open ring systems.

RFI 401 devices can be used as a single unit as well as a part of ROCON hierarchy structure. The ROCON hierarchy structure comprises two levels – local controllers (RFI 401) and work station. The data transfer is done trough an industrial local network.

The dialog with the relay can be done locally by means of an operational interface (situated on the relay’s front panel) or remotely – by means of PC connected and MMI (Man Machine Interface) service program.

Event Recorder and Disturbance Recorder functions are integrated into the device. Communication with SCADA or substation controller equipment (work station) is available. The connection can be done via serial interfaces through the choice of data cable, modem, or optical fibers.

RFI 401 can work together with RDP 101 device (signalization and blocking device). The RDP 101 is a device which ensures the conditions for remote control of the disconnectors and earthing switch.

RFI 401 includes up to 4 selectable setting groups. Transition from one setting group to another can be done during exploitation of the device.
locally - trough the front device's keypad
remotely - by running MMI-service program or by command from work station (SCADA)
via dedicated binary inputs


Relay protection functions

OVERCURRENT PROTECTION (OC)

 

Overcurrent protection with four independent stages
Each stage can be switched ON or OFF

The type of each stage can be:
Definite time delay or Instantaneous overcurrent protection - ANSI 50/51/67
Inverse time delay overcurrent protection - ANSI 51/67TOC with selectable time delay characteristic according to IEC and ANSI standards

Directional or non-directional overcurrent protection stages:
All stages may be set independently from each other for directional or non-directional and combined according to the user's requirements
The maximum sensitivity angle can be configured for
overcurrent protection function in step 1°
Possibility for non-directional relays after remote or manual circuit breaker (CB) closing

Acceleration of overcurrent protection stages:
Possibilities for acceleration from Autoreclosing depending of the cycle
Possibilities for acceleration after remote or manual CB closing

Blocking:
Possibility for block or enable the action of the current elements of each stage separatelly, depending on pick-up of the under voltage relays of the respective phases of the Under voltage protection (UVP)
Possibilities for blocking of each stage separately from an external signal received by dedicated binary inputs
Possibilities for blocking of each stage separately at the different reclosing cycles of the Autoreclosing function
Possibilities for blocking the AR at the trip of each stage.


OVERCURRENT GROUND FAULT PROTECTION (OGFP)
 

Overcurrent ground (earth) fault protection with three independent definite time delay stages - ANSI 50N / 51N / 67N;
Each stage can be switched ON or OFF

Directional or non-directional overcurrent earth fault protection stages
All stages may be set independently from each other “directional” or “non-directional” and combined according to the user's requirements
The maximum sensitivity angle can be configured for overcurrent ground fault protection in step 1 °
Possibility for non-directional relays after remote or manual circuit breaker (CB) closing

Acceleration of overcurrent ground fault protection stages
Possibilities for acceleration from Autoreclosing depending of the cycle
Possibilities for acceleration after remote or manual CB closing

Blocking
Possibilities for blocking of each stage separately from an external signal received by dedicated binary inputs.
Possibilities for blocking of each stage at the different reclosing cycles of the Autoreclosing function
Possibilities for blocking the AR at the trip of each stage

INVERSE TIME DELAY OVERCURRENT GROUND FAULT PROTECTION (ITGF)

 

Inverse time delay overcurrent ground (earth) fault protection - according to ANSI;

51N/67N TOC with selectable time delay characteristic according to IEC and ANSI standards;

Directional or non-directional inverse time overcurrent ground fault protection:
The maximum sensitivity angle can be configured for both functions – the same max. sensitivity angle for inverse time and definite time ground fault protections
Possibility for non-directional relays after remote or manual circuit breaker (CB) closing

Blocking:
Possibilities for blocking of the ITGF from an external signal received by dedicated binary input;
Possibilities for blocking at the different reclosing cycles of the Autoreclosing function
Possibilities for blocking the AR at the trip of the ITGF

NEGATIVE SEQUENCE OVERCURRENT PROTECTION (NSOC)

 

Evaluation of negative sequence component of the currents – ANSI 46;
In line protection, the negative-sequence protection permits detection on the high side of high-resistance phase-to-phase faults and phase-to-earth faults that are on the low side of a transformer. This provides backup protection for high-resistance faults beyond the transformer. To detect the unbalanced load, the ratio negative-sequence current/rated (nominal) current is evaluated;
A measured current element for the negative sequence current - I2;
Timer activated at current measuring element pick-ups;
Possibilities for blocking of the NSOC from an external signal received by dedicated binary input.

THERMAL OVERLOAD PROTECTION (TOL)

 

Uses a thermal model of the line based on its heating and cooling time constants and an exponential law of alteration – ANSI 49;
Monitors the temperature state through the relative temperature which is connected with the squared current of the line;
In case of overload the protection picks-up with a delay which depends on the degree of overload;
The protection has two stages providing trip and pre-trip alarm outputs;
Possibilities for blocking of the TOL from an external signal received by dedicated binary input.

POWER GROUND (EARTH) FAULT PROTECTION (PGF)

 

Capacitive power relay for insulated neutral networks or active power relay for compensated networks – ANSI 50Ns/67Ns;
Timer activated at power measuring element operation (pick-up);
Directional or non-directional protection – pick-ups only at positive values of the power (directional PGF) or at absolute values of the power (non-directional PGF);
Possibilities for blocking of the PGF from an external signal received by dedicated binary input.

UNDERVOLTAGE PROTECTION (UV)

 

Under voltage protection with two independent stages;
Selectable phase-to-phase or phase-to-neutral voltage relays – ANSI 27, 27S;
Three measured voltage elements;
Each stage can be switched ON or OFF;
Possibility for UV function blocking at voltages, beyond the setting range;
Possibility for UV function blocking through the dedicated binary input (at operation of instantaneous overcurrent protection or distance protection on 110 kV level for example.

NEUTRAL VOLTAGE DISPLACEMENT (NVD) or Ground Fault Control (GFC)

 

Residual voltage earth fault protection – ANSI 59N;
A measured voltage element for the residual voltage 3Uo;
Timer activated at voltage measuring element pick-ups;
Possibilities for blocking of the NVD function from an external signal received by dedicated binary input.

OVERVERVOLTAGE PROTECTION (OV)

 

Over voltage protection with two independent stages – ANSI 59;
Each stage can be switched ON or OFF;
Selectable phase-to-phase or phase-to-neutral voltage relays;
Three measured voltage elements;
Timer activated at voltage measuring element operation (pick-up);
Possibilities for blocking of the OV function from an external signal received by dedicated binary input.

NEGATIVE SEQUENCE OVERVOLTAGE PROTECTION (NSOV)

 

Evaluation of negative sequence component of the voltages – ANSI 47;
A measured voltage element for the negative sequence voltage U2;
Timer activated at voltage measuring element pick-ups;
Possibilities for blocking of the NSOV from an external signal received by dedicated binary input.

FREQUENCY PROTECTION (FP)

 

Frequency protection with two independent stages;

Each stage can be switched ON or OFF;

The type of each stage can be:
Under frequency protection - ANSI 81U
Over frequency protection – ANSI 81O

The function is blocked when the measured voltages are very low;

Possibilities for blocking of the FP from an external signal received by dedicated binary input.

AUTORECLOSING

 

Autoreclosing function acc. ANSI 79AR;

Up to 6 shots;

Starting condition:
At the circuit breaker and control switch position discrepancy• at the circuit breaker and control switch position discrepancy
At tripping command: from internal protections; from external protections - by binary inputs; from internal or external protections.

BREAKER FAILURE PROTECTION

 

The breaker failure protection function monitors the reaction of a circuit breaker to a trip signal from of any integrated (internal) and external protections – ANSI 50BF;

Breaker failure detects the tripping command issued. The tripping command can be issued by follow:
Internal relay protection function (activation of the configured binary outputs for tripping);
External relay protection function (activation of a dedicated binary input);

If after a programmable time delay, the circuit breaker has not opened, breaker failure protection issues a trip signal via a super ordinate circuit breaker.

TRIP CIRCUIT SUPERVISION

 

Trip circuit supervision – ANSI 74TC;
One or two binary inputs can be used for monitoring the circuit-breaker trip coils including the connecting cables.
An alarm signal is issued if the circuit is interrupted.

CIRCUIT BREAKER LIFE TIME MONITORING

 

Visualization of the circuit breaker’s phase life time;
Signalization of CB run out of resource;
Possibility for describing of the CB life time curves;
Possibility for editing the CB’s life time value for each phase;


The RFI 401 device has 4 selectable setting groups including all protection and automation functions. Commutation between the separate groups can be achieved locally, remotely or via dedicated binary inputs.


Data acquisition and control

Remote measurement (RM)

  The RFI 401 device measures, processes and archives information about instant and integral values for the analogue quantities of the protected feeder calculates the average “rms” values for each second and sends it to the connected operating station PC.

Remote control (RC)

  The function permits direct control of the feeder's CB in two ways - by means of remote control commands from work station PC (received trough the local network and generated by MMI program) or initiated by pressing of push buttons "I" and "O" situated on the unit's front panel. Two binary outputs are necessary for remote control function operation. The execution of the remote control commands is permitted only if the dedicated "Remote control switch" is turned in "ON" position. The successful command execution is monitored by means of binary input connected to the CB auxiliary contact.

Remote signaling (RS)

 

The device receives processes and archives the following information: :
Change of state of the double-positioned equipment
Alarms from the protection system
Warning alarm for exceeding of limit values
Alarms from external protections and automatics
Alarm at not executed command and at activating of inhibited commands

The information is transferred to the work station PC having it's date and time and it is available on the RFI 401 display.


Event recorder function

  The event recorder memory buffer is designed for up to 2000 records.
Each of the records consists of information about the event type, the real time of its appearance (year, month, day, hour, minute, second, second/1000) and in certain cases – some numerical data characterizing the process recorded.
The information recorded is stored in non-volatile memory and can be shown on the device’s display and/or memorized on the PC running the MMI program.
In the unit’s memory the stored event can be found and displayed using the following attributes:
Last stored event
The events stored during the last hour
The events stored during last 24 hours
The events stored during the last month (up to the same moment in the previous month)
The records stored during the chosen day

Disturbance recorder function

  For each of the event included into the Event recorder can be set to initiate additional more detailed oscillographic data collection. The period of the data collection consist of two intervals pre-history duration and during the fault. These records consist of all measured and calculated analogue values (wave-form), binary inputs and outputs and processing points. The values recorded are measured with maximal sampling frequency of the device. The records from the Disturbance recorder function can be transferred to the connected PC running MMI service program. On the Work station PC (SCADA-system) the information recorded can be added to the archive displayed in graphical way and used for detailed analysis of the primary events and the behavior of the relay protections and primary equipment.

Working in SCADA-system

 

The device can be connected to Work Station in SCADA-system by means of local network. The network is based on RS485 or fiber optic – the respective interface connector is used. The communication protocol is IEC 60870-5-103 (option IEC 61850). The device’s data acquisition and remote control functions are performed by means of work station – measuring, signaling, remote control (opening or closing command to the circuit breaker, disconnecttors, earthing switch).
Additionally by work station facilities the device can be configured its settings parameters, can be read and corrected and all stored into unit’s memory data can be archived. Also all data stored by means of “Disturbance recorder” and “Event recorder” functions can be transferred and archived into WS for farther analysis.

Human Machine Interface (HMI)

 

Device’s HMI interface is situated on the front panel. It consists of:
LCD display – 2 rows, 16 characteristics each. The display has back light illumination (option: graphical monochromatic display)
Indication zone of 9 LED’s (green LED “READY” and 8 red colored S1 – S8 which are free configurable)
Screen blinkers (7 pcs) free configurable
Functional keypad comprising 10 push buttons
PC optic interface zone for positioning of specially designed connection cable


Man Machine Interface - MMI

 

The MMI program is a 32-bit application intended to work under WINDOWS® operational system. The connection between the device and PC running MMI software is done trough RS232 interface by means of specially designed connection cable. The PC interface cable can be connected to PC COM port or to USB port through RS232-USB converter. The connection is fully isolated.
The PC interface cable can be connected to the device in one of two ways: by the serial port CANON 9 type positioned on the left side of the device or by the serial port positioned on the front side of the device (by means of magnet – optical head).
The PC based MMI program is designed to make the configuration and setting of the relay easier. It can fulfill the following functions:
Reviewing, changing, saving and setting of the relay configuration and settings;
Reviewing and saving of information from event recorder and disturbance recorder;
Remote commands such as: changing of the working setting group; synchronizing of the real time clock; LED indicators acknowledgment; clearing of the events stored into the device’s memory; changing the CB life time ect.;
Remote control of the main measuring possibilities of the relay – analogue and binary outputs and LED indicators ;
Analysis and documentation of system faults;
Printing of the setting parameters, configurations, recorded events and distur-bance data saved into the relay memory.

Download MMI program

 

Technical data

POWER SUPPLY

 
Rated voltage, Un

24 … 48 V DC/AC (-20% ... +20%)
24 … 110 V DC (-20% … +10%)
110 V DC/AC (-20% ... +20%)
220 V DC/AC (-20% ... +20%)

DC supply interruption

According to IEC 60255-11:
0,1 s / 100 % at 110/220 V
0,01 s / 100 % at 24 V

Burden

9 W

ANALOG INPUTS

 

Frequency

 

-rated values fn

50 Hz (option 60 Hz)

- operational range

46 ... 52 Hz

Current inputs

6 pcs.

Rated current, In

5 À / 1 À

Consumption

<0,05 VA at In

Thermal current withstand
(acc. IEC 60255-6, IEC 60255-3)

continuous - 10.In,
for 1 s – 100.In
for 10 ms - 250.In

   

Current inputs for data acquisition and control
or/and residual current in RP part (Range 1)

3 pcs,
Range 1: (0,01 ... 1,3).In
   

Current inputs for relay protection part (Range 2)

3 pcs,
Range 2: (0,1 ... 40).In

Voltage inputs

3 pcs

Rated voltage, Un

100 V

Operational range

(0,01...1,3).Un

Consumption at Un

0,1 VA

Continuously Voltage Withstand

2,5.Un

BINARY INPUTS

16 pcs

Auxiliary power supply

 

- Rated voltage

24/48/110/220 V DC

- Operational range

(-20 % … +20 %) Un

Burden in each input circuit

<0,4 W at 110 V DC
<0,75 W at 220 V DC

BINARY OUTPUTS

9 (8+Ready signal)

Electromechanical relays with NO/NC contacts

8 À max
250 V AC / DC max
2 000 VA
< 10 ms operation time

CONSTRUCTION

 

External part Metal welded box

 

Surface mounting

 

Dimensions

320 mm x 370 mm x 55 mm

Weight

4 kg

Protection degree (acc. IEC 60529)

IP52 (front panel)

Flush mounting

 

Dimensions

300 mm x 300 mm x 52 mm

Weight

4 kg

Protection degree (acc. IEC 60529)

IP52 (front panel)

INTERFACES

 

Communication protocols:

IEC 60870-5-103, IEC 60870-5-NEO,
IEC 61850 (option)

Optical interface (option)

10 Mbit/s

RS485 electrical

38,4 kbit/s max

RS232 current loop / optical head

9,6 kbit/s

ELECTRICAL TESTS

 

Insulation Tests

IEC 60255-5, class 3

High Voltage Test

2,5 kV; 50 Hz; 1 min

Impulse Voltage Test

5 kV; 1,2 / 50 ms; 0,5 J

Insulation Resistance Test

>100 MW ; 500 V DC

   

ELECTROMAGNETIC COMPATIBILITY (EMC)

 

EMC – disturbance immunity

 

High frequency disturbance

IEC 60255-22-1; EN 61000-4-12, class 3

Electrostatic Discharge

IIEC 60255-22-2, class 3
EN 61000-4-2, class 4

Radio-frequency Electromagnetic Field:

IEC 60255-22-3; EN 61000-4-3, class 3

Fast Transients

IEC 60255-22-4, class B
EN 61000-4-4, class 4

Surge immunity

IEC 60255-22-5; EN 61000-4-5, class 3

Conductive radio disturbances

IEC 60255-22-6; EN 61000-4-6, class 3

Power frequency magnetic field

EN 61000-4-8, class 4

   

EMC - emissions

IEC CISPR 11, class A

 

 

MECHANICAL TESTS

 

During operation

 

Vibration

IEC 60255-21-1, class 1; IEC 60068-2-6

Shocks

IEC 60255-21-2, class 1; IEC 60068-2-27

Seismic tests

IEC 60255-21-3, class 1, IEC 60068-3-3

During transport (with standard package)

 

Vibrations

IEC 60255-21-1, class 1; IEC 60068-2-6

Shocks

IEC 60255-21-2, class 1; IEC 60068-2-27

Bump

IEC 60068-2-29

AMBIENT CONDITIONS  

During transportation and storage

IEC 60068-2-1; IEC 60068-2-2

– During transportation and storage

-40 ... +70 ° C

– During exploitation

-25 ...+55 ° C

Relative air humidity

IEC 60068-2-78: 95% at 40 ° C

 

Connection diagrams

Open as PDF file - /191 kB/
Optional possibilities

As an option the device can be provided with Signalization and blocking unit, type RDP 101. In such a case the relay capabilities is upgraded with additional 24 binary inputs and 16 binary outputs.