| Description
General information
RFI 401 is intended to be used like a multifunctional relay protection,
automatics and remote control units for middle voltage feeders and also
like back-up protections for low voltage sides of the power transformers.
For line protection, the device can be used in networks with grounded,
low resistance grounded, isolated or compensated neutral point. It is
suitable for radial systems with single-end infeed or open ring systems.
RFI 401 devices can be used as a single
unit as well as a part of ROCON hierarchy structure. The ROCON hierarchy
structure comprises two levels – local controllers (RFI 401) and work
station. The data transfer is done trough an industrial local network.
The dialog with the relay can be done locally by means
of an operational interface (situated on the relay’s front panel) or remotely
– by means of PC connected and MMI (Man Machine Interface) service program.
Event Recorder and Disturbance Recorder
functions are integrated into the device. Communication with SCADA or
substation controller equipment (work station) is available. The connection
can be done via serial interfaces through the choice of data cable, modem,
or optical fibers.
RFI 401 can work together with RDP 101
device (signalization and blocking device). The RDP 101 is a device which
ensures the conditions for remote control of the disconnectors and earthing
switch.
RFI 401 includes
up to 4 selectable setting groups. Transition from one setting group to
another can be done during exploitation of the device.
locally - trough
the front device's keypad
remotely - by running
MMI-service program or by command from work station (SCADA)
via dedicated binary
inputs
Relay protection functions
OVERCURRENT PROTECTION (OC)
OVERCURRENT GROUND FAULT PROTECTION (OGFP)
INVERSE TIME DELAY OVERCURRENT GROUND FAULT PROTECTION
(ITGF)
NEGATIVE SEQUENCE OVERCURRENT PROTECTION (NSOC)
| |
Evaluation of negative
sequence component of the currents – ANSI 46;
In line protection, the negative-sequence protection permits detection
on the high side of high-resistance phase-to-phase faults and phase-to-earth
faults that are on the low side of a transformer. This provides
backup protection for high-resistance faults beyond the transformer.
To detect the unbalanced load, the ratio negative-sequence current/rated
(nominal) current is evaluated;
A measured current element for the negative sequence current - I2;
Timer activated at current measuring element pick-ups;
Possibilities for blocking of the NSOC from an external signal received
by dedicated binary input.
|
THERMAL OVERLOAD PROTECTION (TOL)
| |
Uses a thermal model
of the line based on its heating and cooling time constants and
an exponential law of alteration – ANSI 49;
Monitors the temperature state through the relative temperature
which is connected with the squared current of the line;
In case of overload the protection picks-up with a delay which depends
on the degree of overload;
The protection has two stages providing trip and pre-trip alarm
outputs;
Possibilities for blocking of the TOL from an external signal received
by dedicated binary input.
|
POWER GROUND (EARTH) FAULT PROTECTION (PGF)
| |
Capacitive power relay
for insulated neutral networks or active power relay for compensated
networks – ANSI 50Ns/67Ns;
Timer activated at power measuring element operation (pick-up);
Directional or non-directional protection – pick-ups only at positive
values of the power (directional PGF) or at absolute values of the
power (non-directional PGF);
Possibilities for blocking of the PGF from an external signal received
by dedicated binary input. |
UNDERVOLTAGE PROTECTION (UV)
| |
Under voltage protection
with two independent stages;
Selectable phase-to-phase or phase-to-neutral voltage relays – ANSI
27, 27S;
Three measured voltage elements;
Each stage can be switched ON or OFF;
Possibility for UV function blocking at voltages, beyond the setting
range;
Possibility for UV function blocking through the dedicated binary
input (at operation of instantaneous overcurrent protection or distance
protection on 110 kV level for example. |
NEUTRAL VOLTAGE DISPLACEMENT (NVD) or Ground Fault
Control (GFC)
| |
Residual voltage earth
fault protection – ANSI 59N;
A measured voltage element for the residual voltage 3Uo;
Timer activated at voltage measuring element pick-ups;
Possibilities for blocking of the NVD function from an external
signal received by dedicated binary input. |
OVERVERVOLTAGE PROTECTION (OV)
| |
Over voltage protection
with two independent stages – ANSI 59;
Each stage can be switched ON or OFF;
Selectable phase-to-phase or phase-to-neutral voltage relays;
Three measured voltage elements;
Timer activated at voltage measuring element operation (pick-up);
Possibilities for blocking of the OV function from an external signal
received by dedicated binary input.
|
NEGATIVE SEQUENCE OVERVOLTAGE PROTECTION (NSOV)
| |
Evaluation
of negative sequence component of the voltages – ANSI 47;
A measured voltage element for the negative sequence voltage U2;
Timer activated at voltage measuring element pick-ups;
Possibilities for blocking of the NSOV from an external signal received
by dedicated binary input. |
FREQUENCY PROTECTION (FP)
| |
Frequency
protection with two independent stages;
Each stage can be switched ON or OFF;
The type of each stage can be:
Under frequency
protection - ANSI 81U
Over frequency
protection – ANSI 81O
The function is blocked when the measured voltages are very low;
Possibilities for blocking of the FP from an external signal received
by dedicated binary input.
|
AUTORECLOSING
| |
Autoreclosing
function acc. ANSI 79AR;
Up to 6 shots;
Starting condition:
At the circuit
breaker and control switch position discrepancy• at the circuit
breaker and control switch position discrepancy
At tripping
command: from internal protections; from external protections -
by binary inputs; from internal or external protections.
|
BREAKER FAILURE PROTECTION
| |
The breaker
failure protection function monitors the reaction of a circuit breaker
to a trip signal from of any integrated (internal) and external
protections – ANSI 50BF;
Breaker failure detects the tripping command issued. The tripping
command can be issued by follow:
Internal relay
protection function (activation of the configured binary outputs
for tripping);
External relay
protection function (activation of a dedicated binary input);
If after a programmable time delay, the circuit breaker has not
opened, breaker failure protection issues a trip signal via a super
ordinate circuit breaker.
|
TRIP CIRCUIT SUPERVISION
| |
Trip circuit
supervision – ANSI 74TC;
One or two binary inputs can be used for monitoring the circuit-breaker
trip coils including the connecting cables.
An alarm signal is issued if the circuit is interrupted.
|
CIRCUIT BREAKER LIFE TIME MONITORING
| |
Visualization
of the circuit breaker’s phase life time;
Signalization of CB run out of resource;
Possibility for describing of the CB life time curves;
Possibility for editing the CB’s life time value for each phase;
The RFI 401 device has 4 selectable setting groups including all
protection and automation functions. Commutation between the separate
groups can be achieved locally, remotely or via dedicated binary
inputs.
|
Data acquisition and control
Remote measurement (RM)
| |
The RFI 401 device measures,
processes and archives information about instant and integral values
for the analogue quantities of the protected feeder calculates the
average “rms” values for each second and sends it to the connected
operating station PC. |
Remote control (RC)
| |
The function permits direct
control of the feeder's CB in two ways - by means of remote control
commands from work station PC (received trough the local network and
generated by MMI program) or initiated by pressing of push buttons
"I" and "O" situated on the unit's front panel.
Two binary outputs are necessary for remote control function operation.
The execution of the remote control commands is permitted only if
the dedicated "Remote control switch" is turned in "ON"
position. The successful command execution is monitored by means of
binary input connected to the CB auxiliary contact. |
Remote signaling (RS)
Event recorder function
| |
The event recorder memory
buffer is designed for up to 2000 records.
Each of the records consists of information about the event type,
the real time of its appearance (year, month, day, hour, minute, second,
second/1000) and in certain cases – some numerical data characterizing
the process recorded.
The information recorded is stored in non-volatile memory and can
be shown on the device’s display and/or memorized on the PC running
the MMI program.
In the unit’s memory the stored event can be found and displayed using
the following attributes:
Last stored event
The events stored during the last hour
The events stored during last 24 hours
The events stored during the last month (up to the same moment in
the previous month)
The records
stored during the chosen day |
Disturbance recorder function
| |
For each of the event included
into the Event recorder can be set to initiate additional more detailed
oscillographic data collection. The period of the data collection
consist of two intervals pre-history duration and during the fault.
These records consist of all measured and calculated analogue values
(wave-form), binary inputs and outputs and processing points. The
values recorded are measured with maximal sampling frequency of the
device. The records from the Disturbance recorder function can be
transferred to the connected PC running MMI service program. On the
Work station PC (SCADA-system) the information recorded can be added
to the archive displayed in graphical way and used for detailed analysis
of the primary events and the behavior of the relay protections and
primary equipment. |
Working in SCADA-system
| |
The device can be connected
to Work Station in SCADA-system by means of local network. The network
is based on RS485 or fiber optic – the respective interface connector
is used. The communication protocol is IEC 60870-5-103 (option IEC
61850). The device’s data acquisition and remote control functions
are performed by means of work station – measuring, signaling, remote
control (opening or closing command to the circuit breaker, disconnecttors,
earthing switch).
Additionally by work station facilities the device can be configured
its settings parameters, can be read and corrected and all stored
into unit’s memory data can be archived. Also all data stored by
means of “Disturbance recorder” and “Event recorder” functions can
be transferred and archived into WS for farther analysis. |
Human Machine Interface (HMI)
Man Machine Interface - MMI
Technical data
POWER
SUPPLY |
|
| Rated
voltage, Un |
24
… 48 V DC/AC (-20% ... +20%)
24 … 110 V DC (-20% … +10%)
110 V DC/AC (-20% ... +20%)
220 V DC/AC (-20% ... +20%)
|
DC
supply interruption |
According
to IEC 60255-11:
0,1 s / 100 % at 110/220 V
0,01 s / 100 % at 24 V |
| Burden |
9
W |
| ANALOG
INPUTS |
|
| Frequency |
|
| -rated
values fn |
50
Hz (option 60 Hz) |
| -
operational range |
46
... 52 Hz |
| Current
inputs |
6 pcs. |
| Rated current, In |
5 À / 1 À |
| Consumption |
<0,05 VA at In |
| Thermal current withstand
(acc. IEC 60255-6, IEC 60255-3) |
continuous - 10.In,
for 1 s – 100.In
for 10 ms - 250.In |
| |
|
| Current inputs for data acquisition and control
or/and residual current in RP part (Range 1) |
3 pcs,
Range 1: (0,01 ... 1,3).In |
| |
|
| Current inputs for relay protection part (Range 2) |
3 pcs,
Range 2: (0,1 ... 40).In |
Voltage
inputs |
3
pcs |
| Rated voltage, Un |
100
V |
| Operational
range |
(0,01...1,3).Un
|
| Consumption at Un |
0,1 VA |
| Continuously Voltage Withstand |
2,5.Un
|
| BINARY
INPUTS |
16
pcs |
| Auxiliary
power supply |
|
-
Rated voltage |
24/48/110/220
V DC |
| -
Operational range |
(-20 % … +20 %) Un |
| Burden in each input circuit |
<0,4 W at 110 V DC
<0,75 W at 220 V DC |
BINARY
OUTPUTS |
9
(8+Ready signal) |
Electromechanical relays with NO/NC contacts |
8
À max
250 V
AC / DC max
2 000
VA
< 10
ms operation time |
| CONSTRUCTION |
|
| External part Metal
welded box |
|
| Surface mounting |
|
| Dimensions |
320 mm x 370 mm x 55
mm |
| Weight |
4 kg |
| Protection degree (acc.
IEC 60529) |
IP52 (front panel) |
| Flush mounting |
|
| Dimensions |
300 mm x 300 mm x 52 mm |
| Weight |
4 kg |
| Protection degree (acc. IEC 60529) |
IP52 (front panel) |
| INTERFACES |
|
| Communication
protocols: |
IEC 60870-5-103, IEC 60870-5-NEO,
IEC 61850 (option) |
| Optical interface (option) |
10 Mbit/s |
| RS485 electrical |
38,4 kbit/s max |
| RS232
current loop / optical head |
9,6
kbit/s |
| ELECTRICAL
TESTS |
|
| Insulation
Tests |
IEC
60255-5, class 3 |
| High
Voltage Test |
2,5
kV; 50 Hz; 1 min |
| Impulse Voltage Test |
5
kV; 1,2 / 50 ms; 0,5 J |
|
Insulation Resistance Test |
>100
MW ; 500 V DC |
| |
|
| ELECTROMAGNETIC
COMPATIBILITY (EMC) |
|
| EMC
– disturbance immunity |
|
| High frequency disturbance |
IEC
60255-22-1; EN 61000-4-12, class 3 |
| Electrostatic
Discharge |
IIEC
60255-22-2, class 3
EN 61000-4-2, class 4 |
| Radio-frequency Electromagnetic Field: |
IEC
60255-22-3; EN 61000-4-3, class 3 |
| Fast Transients |
IEC
60255-22-4, class B
EN 61000-4-4, class 4 |
| Surge
immunity |
IEC
60255-22-5; EN 61000-4-5, class 3 |
| Conductive
radio disturbances |
IEC
60255-22-6; EN 61000-4-6, class 3 |
| Power frequency magnetic field |
EN
61000-4-8, class 4 |
| |
|
| EMC
- emissions |
IEC
CISPR 11, class A |
| |
|
| MECHANICAL
TESTS |
|
| During operation |
|
| Vibration |
IEC
60255-21-1, class 1; IEC 60068-2-6 |
| Shocks |
IEC
60255-21-2, class 1; IEC 60068-2-27 |
| Seismic tests |
IEC
60255-21-3, class 1, IEC 60068-3-3 |
| During
transport (with standard package) |
|
| Vibrations |
IEC
60255-21-1, class 1; IEC 60068-2-6 |
| Shocks |
IEC
60255-21-2, class 1; IEC 60068-2-27 |
| Bump |
IEC
60068-2-29 |
| AMBIENT
CONDITIONS |
|
| During
transportation and storage |
IEC 60068-2-1;
IEC 60068-2-2 |
| –
During transportation and storage |
-40
... +70 ° C |
| –
During exploitation |
-25
...+55 ° C |
| Relative air humidity |
IEC
60068-2-78: 95% at 40 ° C |
|