| Description
General information
RFI 421 is intended to be used like a relay protection, automatics
and remote control units of follow purposes:
Medium voltage overhead
distribution lines
Medium voltage sides
of the power transformers
Back-up protection
for high voltage side of the power transformers
Motor protection
and ect.
Event Recorder and Disturbance Recorder
functions are integrated into the device. Communication with SCADA or
substation controller equipment (work station) is available. The connection
can be done via serial interfaces through the choice of data cable, modem,
or optical fibers.
RFI 421 includes
up to 4 selectable setting groups. Transition from one setting group to
another can be done during exploitation of the device.
locally - trough
the front device's keypad
remotely - by running
MMI-service program or by command from work station
via dedicated binary
inputs
Relay protection functions
Definite time delay overcurrent protection (ANSI
50, 51)
Instantaneous overcurrent protection (ANSI 50, 51)
Inverse time delay overcurrent protection (ANSI 51)
| |
Non-directional inverse
time delay over-current protection
Selectable time delay characteristic according to IEC and ANSI standards:
According IEC: Inverse time, Very Inverse, Extremely Inverse,
Long Inverse, RI Inverse
According ANSI: Long Inverse, Moderately Inverse, Very Inverse,
Extremely Inverse, Isquared T
General settings
Curent relays
type - phase or phse-tophse relays
Setting Is,pick-up
- (0,10 ... 10,00).In
Current delay
time ratio Ks - 0,05 ... 5,00 s
Operating time: < 30 ms |
Overcurrent earth fault protection (ANSI 50N, 51N)
| |
Non-directional ground-fault
protection with definite time delay;
Up to 3 stages and possibility for switching ON or OFF for each
stage separately;
Possibility for acceleration at autoreclosing for each stage separately;
Possibility for acceleration in case of remote or manual CB closing
for each stage separately.
Residual current relay - settings
Stage 1 - (0,10 ... 100,00)Iîn
Stage 2 - (0,10 ... 100,00)Iîn
Stage 3 - (0,10 ... 100,00)Iîn
Time delay - settings:
Stage 1 - 0,00 ... 100,00 s
Stage 2 - 0,00 ... 100,00 s
Stage 3 - 0,00 ... 100,00 s |
Inverse time delay earth fault protection (ANSI
51N)
| |
Non-directional inverse
time delay earth fault protection;
Selectable time delay characteristic according to IEC and ANSI standards:
According IEC: Inverse time, Very Inverse, Extremely Inverse,
Long Inverse, RI Inverse
According ANSI: Long Inverse, Moderately Inverse, Very Inverse,
Extremely Inverse, Isquared T
Settings
Curent relays
type - phase or phse-tophse relays
Setting Is,pick-up
- (0,10 ... 10,00).In
Current delay
time ratio Ks - 0,05 ... 5,00 s
Operating time: < 30 msÍàñòðîéêà íà òîêîâîòî ðåëå |
Thermal overload protection (ANSI 49)
Negative sequence overcurrent protection (ANSI 46)
| |
Evaluation of negative
sequence component of the currents;
In line protection, the negative-sequence protection permits detection
on the high side of high-resistance phase-to-phase faults and phase-to-earth
faults that are on the low side of a transformer (e.g. with the
switch group ?y 5). This provides backup protection for high-resistance
faults beyond the transformer. To detect the unbalanced load, the
ratio.
Settings
Current relayl:
(0,1 ... 20,00).In
Tripping delay
time setting - 0 ... 100 s
Operating time: < 30 ms
|
Autoreclosing (ANSI 79)
| |
Up to six shot AR:
AR starting conditions - at tripping command issued of internal
or external protection function or at the circuit breaker and control
switch positions discrepancy.
AR blocking conditions - tripping by load shedding or other external
equipment, manual closing of the circuit breaker or remote remote
control command for closing or opening the breaker. |
Breaker failure protection (50 BF)
| |
The breaker failure protection
function monitors the reaction of a circuit breaker to a trip signal
from of any integrated (internal) protection;
Breaker failure detects activation of the configured binary outputs
If after a programmable time delay, the circuit breaker has not
opened, breaker failure protection issues a trip signal via a super
ordinate circuit breaker |
Circuit breaker life time monitoring
| |
Visualization
of the circuit breaker’s phase life time
Signalization of CB run out of resource
Possibility for describing of the CB life time curve
Possibility for editing the CB’s life time value for each phase
Each protection function can be set ON or OFF.
|
Data aquisition & remote control functions
Remote measurement
| |
Measures, processes and
archives information about instant and integral values for the analogue
quantities of the protected feeder;
Calculates the average “rms” values of the voltage for each second
and sends them through the local network to the connected PC work
station (WS)
Sends the data to the WS for maximal registered values
The measured analogue values are displayed continuously on the LCD
of the device. |
Remote control
| |
The function permits direct
control of the feeder’s circuit breaker and disconnectors in two ways
– by means of SCADA-system (remote control commands from work station
PC received trough the local network) or initiated by pressing of
spatially designed push buttons “I” and “O” situated on the device’s
front panel. |
Remote signalization
RFI 421 receives processes and archives the
following information:
Primary equipment
status change
Warning and alarm
signalization received from external devices for relay protection and
automation – operation of load shedding relays and auxiliary power supply
failure relays, for example
Pick-up and drop-off
of the voltage relays of the internal relay protection functions
Trip commands sent
to the CB from internal relay protection functions
Alarm signalization
related to the remote control function operation (CB or disconnectors)
– failure in execution of the remote control command, attempt for not
permitted command issuing and etc.
Signalizations for controlled values limit overreaching
The device time synchronizations (by front panel or remotely)
Changing of the working parameters of the device (new configuration, new
re-lay protection settings and new parameters for remote control functions)
Clearing of the data from Event Recorder or Disturbance recorder
Event Recorder function
Disturbance Recorder function
| |
For each of the event included
into the Event recorder can be set to initiate additional more detailed
oscillographic data collection. The period of the data collection
consist of two intervals pre-history duration and during the fault.
These records consist of all measured and calculated analogue values
(wave-form), binary inputs and outputs and processing points. The
values recorded are measured with maximal sampling frequency of the
device. The records from the Disturbance recorder function can be
transferred to the connected PC running MMI service program. On the
Work station PC (SCADA-system) the information recorded can be added
to the archive displayed in graphical way and used for detailed analysis
of the primary events and the behavior of the relay protections and
primary equipment. |
Working in SCADA-system
| |
The device can be connected
to Work Station in SCADA-system by means of local network. The network
is based on RS485 or fiber optic – the respective interface connector
is used. The communication protocol is IEC 60870-5-103 / IEC 61850.
The device’s data acquisition and remote control functions are performed
by means of work station – measuring, signaling, remote control
(opening or closing command to the circuit breaker, disconnecttors,
earthing switch).
Additionally by work station facilities the device can be configured
its settings parameters, can be read and corrected and all stored
into unit’s memory data can be archived. Also all data stored by
means of “Disturbance recorder” and “Event recorder” functions can
be transferred and archived into WS for farther analysis. |
Human Machine Interface (HMI)
Man Machine Interface - MMI
|